indirectly heated tanks 120 – 500 L

Indirectly heated vertical hot water tanks are among other things applied in combination with gas, oil and pellet fired boilers and for district heating. The hot water tanks are made of high grade stainless steel and have a long lifetime. The diabolo-shaped heating coil enables an efficient heat exchange and a quick reheat time. As a result, a large capacity of hot water is supplied for an optimal performance. The 100 % pickled and passivated hot water tanks are maintenance free and because of their lightness in weight easy to install.
DEJONG hot water tanks

indirectly heated hot water tanks 120 to 500 L

M 120-500120150200300400500
Article numberwhite855-0631
silver855-0540855-0541855-0543855-0544855-0545
Part
ACold water inletR3/4"3/4"3/4"1"1"1"
BTo boiler returnR3/4"3/4"3/4"1"1"1"
CFrom boiler supplyR3/4"3/4"3/4"1"1"1"
DImmersion heaterG1 ½"1 ½"1 ½"
ECirculationRp3/4"3/4"3/4"3/4"3/4"3/4"
FHot water outletR3/4"3/4"3/4"1"1"1"
GThermostatG1/2"1/2"1/2"1/2"1/2"1/2"
HThermometerG1/2"1/2"1/2"1/2"1/2"1/2"
IClean out covermm80,5 x 9580,5 x 9580,5 x 9580,5 x 9580,5 x 9580,5 x 95
JHeight insulation incl.mm99411851487180417102020
Tilting heightmm111812841559188518452129
Diameter insulation excl.mm450450450500600600
KDiameter insulation incl. *mm595595595675795795
* Attention, isolation is not demountable!

technical data indirectly heated hot water tanks 120 to 500 L

technical data120150200300400500
Subject to change. No rights can be derived from the content of this website.
Net volumeL119148194296372479
Weightkg232734486977
Max. working pressure tankbar101010101010
Max. working pressure coilbar404040404040
Max. working temperature tank°C959595959595
InsulationNeoporNeoporNeoporNeoporNeoporNeopor
mm707070859595
Heat loss EN 12897Watt333847546069
Energy classAABBBB
Heating coil
Heating surface0,60,70,91,31,61,6
Continuous capacity DIN 4708kW263039556568
Hot water capacity 10-45°Cl/h645736959136816061678
Hot water flowm³/h2222,533,5
Pressure lossmbar6980111238133172
Scale drawing downloadClick here
Click here
Click here
Click here
Click here
Click here
Dimensions chart M120-500:
ACold water inletmm505050535555
BTo boilet returnmm505050535555
CFrom boiler supplymm390450553658690690
DImmersion heatermm---798745745
ECirculationmm6188081110129312281523
FHot water outletmm7489381240154314131723
GThermostatmm293353378458490490
HThermometermm7489381240154314131723